Utility requirements
Power, air and ventilation per machine type, for the people who plan the plant.
| Machine | Electrical | Compressed air | Dust collection | Footprint | Height |
|---|---|---|---|---|---|
| Tumble drum deflash (DEF-DB-2.5) | 460 V 3ph, 30 A | 10 CFM @ 80 PSI | 600 CFM | 72 × 60 in | 120 in |
| Tumble belt deflash (DEF-TMB-3.5) | 460 V 3ph, 30 A | 15 CFM @ 80 PSI | 900 CFM @ 6 in | 59 × 70 in | 11 ft 5 in |
| Wire mesh belt deflash (DEF-WMB-12/20) | 460 V 3ph, 40 to 60 A | 20 CFM @ 80 PSI | 1,200 to 2,000 CFM | 6 to 10 ft × 20 to 30 ft | 10 to 12 ft |
| Dual-station indexer (DEF-INDEX-2240) | 460 V 3ph, 30 A | 20 CFM @ 80 PSI | 800 CFM | 8 × 8 ft | 10 ft |
| Table blast | 460 V 3ph, 60 to 100 A | 10 CFM @ 80 PSI | 2,000 to 3,000 CFM | 10 × 12 ft | 14 to 16 ft |
| Spinner hanger | 460 V 3ph, 60 to 125 A | 10 CFM @ 80 PSI | 2,500 to 4,000 CFM | 10 × 14 ft | 16 to 18 ft |
| Plate and structural line | 460 V 3ph, 100 to 250 A | 30 CFM @ 80 PSI | 4,000 to 8,000 CFM | 12 × 40 to 80 ft | 16 to 20 ft |
| Air blast cabinet | 120/460 V, 15 to 30 A | 50 to 150 CFM per nozzle | 600 to 1,200 CFM | 4 × 6 ft | 7 ft |
| Air blast booth | 460 V 3ph, 60 to 150 A | 150 to 250 CFM per nozzle | 6,000 to 20,000 CFM | Sized to part | 12 to 20 ft |
Planning values for budgeting and plant layout. Published model data (DEF-TMB-3.5: 900 CFM at 6 in, 15 CFM at 80 PSI, 460 VAC / 24 VDC) is exact; the rest are typical planning ranges. The GA drawing for your machine governs.